Type
|
VTCH-N series
|
Control Method
|
|
6-arm phase control | |
Setting method
|
Current signal: DC4 to 20mA (Input impedance: 250Ω) |
Voltage signal: DC1 to 5V (Input impedance: 82kΩ) | |
External manual setting device: 1kΩ | |
Number of phases | 3-phase |
Frequency | 50/60Hz |
Rated Circuit Voltage | 200~440V |
Voltage Adjustment Range | 0–98% |
Rated Current | 30, 60, 80, 100, 150, 200A |
Ambient temperature | 0 to 60°C (current reduced at ambient temperatures above 40°C) |
Insulation resistance
|
50MΩ or more at DC500V megger |
Between current terminal and case, between signal terminal and case, between current terminal and signal terminal, between FAN power terminal and case | |
Dielectric Strength
|
[AC1.5kV (1 minute)] |
Between current terminal and case | |
Current terminal-between case | |
Between signal terminal and case | |
Signal terminal-between case | |
Between current terminal and signal terminal | |
Current terminal-between signal terminal | |
(Between fan power terminal and case: AC1.5kV for 1 minute) | |
[AC2.0kV (1 minute)] | |
Between current terminal and case | |
Current terminal-between case | |
Between signal terminal and case | |
Signal terminal-between case | |
Between current terminal and signal terminal | |
Current terminal-between signal terminal | |
(Between fan power terminal and case: AC1.5kV for 1 minute) |
VTCH-N | ||||
Model
|
Rated Current
|
Rated Input Voltage
|
Body dimensions
W x H x D (mm) |
Mass
|
[VTCH-030-N] |
30
|
200/200V
|
158.5×307×187
|
No options: 4.1kg |
(A) Availability of options | With options: 4.4kg | |||
(B) Presence or absence of fuse | ||||
[VTCH-060-N] |
60
|
Equivalent to the above
|
176×365×262
|
No options: 7.8kg |
(A) Availability of options | With options: 8.1kg | |||
(B) Presence or absence of fuse | ||||
- | - | - | - | - |
[VTCH-100-N] |
100
|
Equivalent to the above
|
196×390×273.6
|
No options: 10.3 kg |
(A) Availability of options | With options: 10.6 kg | |||
(B) Presence or absence of fuse | ||||
[VTCH-150-N] |
150
|
Equivalent to the above
|
196×435×276.5
|
No options: 10.9 kg |
(A) Availability of options | With options: 11.2kg | |||
(B) Presence or absence of fuse | ||||
[VTCH-200-N] |
200
|
Equivalent to the above
|
248×430×329
|
No options: 15.0 kg |
(A) Availability of options | With options: 15.5kg | |||
(B) Presence or absence of fuse |
VTEH-N, VTFH-N types | ||||
Model
|
Rated Current
|
Rated Input Voltage
|
Body dimensions
W x H x D (mm) |
Mass
|
[VTEH-030-N] |
30
|
[VTEH380V] |
158.5×307×187
|
No options: 4.1kg |
[VTFH-030-N] | With options: 4.4kg | |||
(A) Availability of options | [VTFH400/440V] | |||
(B) Presence or absence of fuse | ||||
[VTEH-060-N] |
60
|
Equivalent to the above
|
176×365×262
|
No options: 7.8kg |
[VTFH-060-N] | With options: 8.1kg | |||
(A) Availability of options | ||||
(B) Presence or absence of fuse | ||||
- | - | - | - | - |
[VTEH-100-N] |
100
|
Equivalent to the above
|
196×390×273.6
|
No options: 10.3 kg |
[VTFH-100-N] | With options: 10.6 kg | |||
(A) Availability of options | ||||
(B) Presence or absence of fuse | ||||
[VTEH-150-N] |
150
|
Equivalent to the above
|
196×435×276.5
|
No options: 10.9 kg |
[VTFH-150-N] | With options: 11.2kg | |||
(A) Availability of options | ||||
(B) Presence or absence of fuse | ||||
[VTEH-200-N] |
200
|
Equivalent to the above
|
248×430×329
|
No options: 15.0 kg |
[VTFH-200-N] | With options: 15.5kg | |||
(A) Availability of options | ||||
(B) Presence or absence of fuse |
■Various optional features■
[Constant current control]
The voltage is automatically adjusted to the set current value.
The constant current accuracy is ±3% or less (constant load) for a power supply fluctuation of ±10% / ±5% or less (constant power supply voltage) for a load fluctuation of 5 times.
Built-in voltage limiter / gate is turned off at peak overcurrent and alarm indicator is turned on.
[Constant voltage control]
The voltage is automatically adjusted to the set voltage value. (It cannot be adjusted above the circuit voltage.)
The constant voltage accuracy is within ±3% (constant load) for a power supply fluctuation of ±10%.
Built-in current limiter/gate turns off at peak overcurrent and alarm indicator lights up.
[Peak overcurrent alarm]
When the gate is turned off due to peak overcurrent, an alarm signal is output.
[Heater break alarm]
Detects heater breakage and outputs an alarm signal.
The number of heaters in parallel can be detected up to 2 for delta load and up to 1 for star load. By
detecting voltage and current, it will not malfunction even if the voltage applied to the heater changes from 0 to 100%.